ASHRAE TC 9.9, "Mission Critical Facilities", members are IT folks, and they have defined a Category/Class "A4" that have dry-bulb operating temperatures in the 5-45˚C range:

* https://www.upsite.com/blog/the-importance-of-mutual-underst...

There's also:

> For those familiar with the liquid cooling guidelines, the most obvious change will be that of the Liquid Cooling class designations. Previously, the classes were designated W1, W2, W3, W4 and W5. Each of those classes had a lower temperature limit of 2°C, while the upper limits were 17°C, 27°C, 32°C, 45°C, and Over 45°C respectively. The deficiency in the original designations didn’t really appear until the debate began over adding a class between 32°C and 45°C.

> […] In the end, due to the need for enhanced flexibility, not to mention making it easier for users to remember what temperature goes with the Class, the 5th Edition redesignated the classes based on their upper temperature limit – therefore the classes are now W17, W27, W32, NEW class W40, W45, and the now named W+.

* https://www.upsite.com/blog/what-you-need-to-know-about-ashr...

So >35C isn't entirely unknown already.

* https://www.ashrae.org/technical-resources/bookstore/datacom...